This product is compatible with the PFC-4064.FeaturesAllows for communication to Monitoring StationCommunicates using SIA-DCS or Ademco Contact ID ProtocolsFor use with IPA, AFC, and ARC series Addressable Panels and PFC-4064 Conventional PanelStatus LEDs indicate operation of DACT cardInstalls with ease behind main panel LCD display via User Interface bracketDevice address is set internally to address 1Includes two (2) RJ45 phone cordsDescriptionThe UD-2000 Digital Alarm Communicator Transmitter (DACT) provides for up to two (2) phone lines for communication to a monitoring station. The UD-2000 communicates using the SIADCS or Ademco Contact ID protocols. When enabled, the DACT automatically monitors each phone line or voltage and has the ability to seize the line and connect with a remote receiver. Once the communication is complete, the DACT will hang up.The DACT is provided with terminal blocks for each phone line and two RJ45 cords. In order for the DACT to work properly, it must be installed on a plain old telephone service (POTS) line or equivalent deemed by the authority having jurisdiction. The DACT must be installed before any other equipment to ensure it can seize the phone line.Phone lines are high voltage and should be run in a separate conduit from other circuits. The wire conductors connecting the DACT to the phone system should be 26 AWG or larger.